Intelligence Report

RepWars

DOS Technical Services

No strainer should be used in a fire line without the approval of the Owner’s Insurance Underwriters and/or the Authority Having Jurisdiction.

 

Leading Manufacturers

Ames

 

Conbraco

 

Febco

 

Flomatic

 

Watts Regulator

 

Zurn/Wilkins

 
 

BACKFLOW PREVENTION ASSEMBLY INSTALLATIONS

 

This information reflects accepted design considerations based on experience in implementing cross connection control programs and policies set forth by the American Water Works Association, Environmental Protection Agency, USC Foundation for Cross Connection Control and Hydraulic Research and various state and local health departments. These recommendations outline what an acceptable design and installation constitutes and are to be reasonably interpreted.

 

General Installation And Clearances

 

All double check valve (DCV) and reduced pressure zone (RPZ) backflow prevention assemblies are designed for in-line service and must be installed to prevent freezing, flooding and mechanical damage with adequate space to facilitate maintenance and testing. Ideally, the installation should not require platforms, ladders or lifts for access. Adequate clearances from floors, ceilings and walls must be provided to access the test cocks and to allow the repair and/or removal of the relief valve and check valves; as follows:

 

o         All assemblies should be installed with a centerline height from 30 inches to 60 inches above the floor or adjacent grade. Any installation at a greater height should be provided with a fixed platform, a portable scaffold or a lift meeting OSHA standards.

 

o         A minimum of 12 inches of clear space should be maintained above the assembly to allow for servicing check valves and for operation of shut-off valves.

 

o         A minimum of 30 inches of clear space should be maintained between the front side of the device and the nearest wall or obstruction.

 

o         At least 8 inches clearance should be maintained from the back side of the device to the nearest wall or obstruction. This clearance may need to be increased for models that have side mounted test cocks or relief valves that would be facing the back wall.

 

o         All RPZ devices must have an 18 inch minimum clearance between the bottom of the relief valve and the floor to prevent submersion and to provide access for servicing and relief valve operation.

 

 Miscellaneous Considerations

 

1.          All assemblies should be adequately supported and/or restrained to prevent lateral movement. Pipe hangers, braces, saddles, stanchions, piers, etc., should be used to support the device and should be placed in a manner that will not obstruct the function of or access to the relief valve.

 

2.          Strainers are recommended prior to each backflow prevention assembly on non-fire fighting water lines. No strainer is to be used in a fire line without the approval of the Owner’s Insurance Underwriters and/or the Authority Having Jurisdiction.

 

3.          The assembly should be sized hydraulically, taking into account both the volume requirements of the service and the head loss of the assembly. The head loss of the assembly is not necessarily directed proportional to flow. (Refer to the manufacturers head loss curves).

 

4.          Before selection and installation, refer to manufacturers literature for temperature ranges. All assemblies must be protected from freezing temperatures and if installed where temperatures will reach 100 degrees F or above, a hot water type assembly must be used. Consult manufacturers specifications for recommendations.

 

5.          Thermal water expansion and/or water hammer downstream of the assembly can cause excessive pressure. To avoid possible damage to the system and assembly, use water hammer arresters, surge protectors or expansion tanks as appropriate.

 

6.          All assemblies should be specified and installed with the manufacturer supplied resilient seated shut-off valves integral to the assembly.

 

7.          Water lines should be thoroughly flushed before installing the assembly. Most test failures on new installations are the result of debris fouling one of the check valves or the relief valve.

 

8.          All assemblies must be installed horizontally unless they are specifically approved for vertical installation.

 

9.          Parallel installations should be considered where water service cannot be interrupted and on water lines larger than 4 inches.

 

10.      Assemblies should not be installed in areas containing corrosive, toxic or poisonous fumes or gases which could render the assembly inoperable or pose a safety hazard to personnel.

 

11.      Because of the inherent design of a reduced pressure backflow assembly, fluctuating supply pressure on an extremely low flow or static flow condition may cause nuisance dripping and potential fouling of the assembly. While not effective in all cases, the installation of a soft seated check valve immediately ahead of the RPZ will often hold the pressure constant to the assembly in times of fluctuating supply pressure.

 

12.      Where the distance between the water meter and the device is greater than 10 feet, all exposed piping should be stenciled "Feed Line to Backflow Preventer – DO NOT TAP" at 5 foot intervals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Most test failures on new installations are the result of debris fouling one of the check valves or the relief valve.

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


 

 

 

 

 

Drainage Provisions

 

Drainage for backflow prevention assemblies should be provided for all installations of DCV or RPZ to accommodate discharge during testing or draining of the unit and for RPZ relief valve discharges, as follows:

 

1.          For RPZ devices, drainage capacity should be sized to accommodate both intermittent discharges and a catastrophic failure of the relief valve. Refer to manufacturers flow curves to determine maximum discharge rate based on supply pressure or on-site pressure; whichever is greater.

 

2.          Discharge from relief valves must be readily detectable to maintenance personnel either visually or by means of water level alarms, flow indicator lights, etc.

 

3.          All drainage from RPZ’s must be by gravity drains. Sump pumps should not be relied upon unless they are sized to accommodate the maximum discharge rate and connected to emergency power supplies.

 

4.          An air gap must be maintained between the RPZ relief valve opening and any discharge piping. The air gap must be at least twice the dimension of the effective opening of the relief valve; but in no case less than 1 inch.

 

5.          Manufacturer’s air gap fittings may be utilized provided that they maintain a proper air gap and do not enclose or cover the relief valve. These fittings are only sized to handle intermittent and low flow discharges. Additional drainage capacity may be required to accommodate a catastrophic relief valve failure.

 

6.          Discharge piping from relief valves should be terminated a minimum of one inch above any floor drain or other receiving receptacle.

 

7.          Interior storm sewer drains receiving discharge should be equipped with backwater check valve.

 

8.          Sanitary sewer drains receiving discharge should be trapped and vented.

 

9.          Exterior discharge piping must be terminated above grade in an area not subject to flooding (generally one foot above the 100 year flood elevation). The terminal end of the discharge piping must have a rodent screen and securely supported.

 

10.      All exterior discharge terminals should be screened and kept free of debris, ice, snow or any other obstructions that could inhibit discharge flow.

 

Pit Installations

Primarily due to considerations for access, safety and gravity drainage, it is preferred that backflow prevention devices not be installed in pits. Where pit installations are proposed, however, they should be designed:

o         To be watertight with gasketed manholes or access doors extending a minimum of 6 inches above grade and located to allow natural light into the pit during testing/maintenance.

o         With stairways, ladders or step irons.

o         For crane access for installing and removing large assemblies.

o         With adequate horizontal and vertical clearances to allow access to the device.

o         With a full flow screened gravity drain terminating above grade for all RPZ installations.

o         With sump pumps or gravity daylight drains for all DCV installations.

o         With floors pitched to drain.

o         With adequate ground cover to prevent freezing.

o         With surface grading to divert runoff away from the entrance way.

o         Semi-buried pits for berm installations may be necessary to satisfy gravity drainage requirements.

 

Exterior Above Grade Installations

An above grade installation is generally necessary to provide gravity drainage from RPZ devices. The additional benefits of improved access and enhanced safety are also realized with an above grade installation. Two companies, "Hot Box" and "Hydrocowl", have designed prefabricated insulated enclosures that provide heat, gravity drainage and removable access panels for servicing and testing. As an alternate, wood frame, fiberglass, steel, masonry or precast concrete structures may be utilized. All enclosures should be designed:

o         With a floor elevation that is at least 6 inches above finished grade.

o         To provide adequate clearances around the device to access the test cocks, shutoff valves, check valves and relief valve.

o         With electric heaters or heat trace wire for any water service used year round.

o         With provisions for natural or artificial light.

o         With full flow gravity drains according to the drainage requirements.

o         With security measures such as locking doors and panels, flow alarms or flow indictor lights, power indicator lights, etc.

 

All assemblies must be protected from freezing temperatures and if installed where temperatures will reach 100 degrees F or above, a hot water type assembly must be used.

 

Installation Within A Building

Where containment at the property line cannot be achieved or is waived based on extenuating circumstances, installation within a building is often desirable as the unit can be installed in a mechanical room or other area that has heat and light. Access and drainage considerations must also be satisfied and the devices should be located to avoid physical damage, electrical panels, areas of excessive heat, etc.

Interior installations above grade level should be provided with adequate clearances. Discharge can be directed to adequately sized floor drains or through an exterior wall above grade and screened.

 

Interior below grade or basement installations are acceptable for DCV’s. RPZ’s are only allowed below grade where one or more of the following conditions can be met:

 

o         Where an adequate gravity drainage system is provided to accommodate a relief valve failure.

o         Where water level alarms are installed to detect flow from the device and alert maintenance or security personnel.

o         Where sump pumps are sized to accommodate a relief valve failure and are connected to emergency power.

o         Where the floor area and volume below the device could accommodate discharge from a relief valve failure. For 2 inch and smaller units, 2,000 cubic feet is generally acceptable. For larger units, the time to submerge the device based on the maximum discharge rate and floor area/volume should be no less than 8 hours.

In any of the above cases, the Facility Owner must be made aware of the potential for water damage in the event of a discharge.

 

 

Drawings

Plans and specifications for the installation of backflow prevention assemblies should include the following:

1.          A site plan (to scale or with dimensions) of the facility containing a general location map, name and address of facility, property lines, buildings, the size and location of public water main(s) and all fire and domestic water services, meter pits, yard piping and hydrants, pumper connection(s), interconnections, and the location of the proposed backflow preventer(s).

2.          A plumbing floor plan (plan view) or partial floor plan indicating water services, proposed backflow preventer(s), booster pump system, floor drain(s) and all nearby objects (examples: electrical panels, boilers, chillers, storage tanks, fire pumps, fire sprinkler risers, etc.). The plan must be drawn to scale or with dimensions indicated distance from walls and all nearby objects.

3.          A vertical cross section(s) of the proposed installation with elevations from floor, ceiling, outside grade and all nearby objects.

 

 

 

Design Information

The Plumbing Engineer should provide the following design information to the Facility Owner for operations and maintenance of the water systems:

o         General use of water within the facility.

o         The degree of hazard for each BFP device.

o         Detailed explanation of BFP drainage provisions.

o         Size and description of all fire and domestic water services.

o         Actual or estimated maximum flow demand.

o         Pressures – upstream and downstream of the backflow preventer during peak design flow.

o         Description of the fire fighting system.

o         Description of the installation of the backflow preventer – indicate the location of backflow preventer, drainage, lighting, heating, access to unit.

o         The elevation and location of the 100 year flood plain in relation to the BFP. A reduced pressure zone backflow preventer must generally be installed 1 foot above the 100 year flood plain elevation.

o         Description of the booster pump system, answering the following questions:

1.          After the installation of the proposed backflow preventer(s), will the Net Positive Suction Head (NPSH) required for the proper operation of the booster pump system be adequate?

2.         After the installation of the backflow preventer(s) in the suction line to the booster pump system, will the booster pump system operate properly at peak demand to deliver adequate pressure to the highest elevation and/or most remote fixture unit or any other operation requiring a certain pressure?

 

 

 

 

RepWars

Copyright © 1997 - 2006

DOS Technical Services

All Rights Reserved

 

Certification and Testing

After an approval of plans has been issued and the assembly has been installed, it must be tested by a certified tester. The Plumbing Engineer is then responsible to certify that the installation complies with the approved plans and specifications.

Assemblies must be tested at least annually by a certified tester with the results recorded.